Measurement of solubility and water content of insulating oils for HV XLPE cable terminations

Bidragsytere:
  • Knut Brede Liland

Bok

Om resultatet

Vitenskapelig Kapittel/Artikkel/Konferanseartikkel
Publiseringsår: 2008

Importkilder

SINTEF AS-ID: S7260

Beskrivelse Beskrivelse

Tittel

Measurement of solubility and water content of insulating oils for HV XLPE cable terminations

Sammendrag

Water has been found to be one of the the main causes for some service breakdowns of high voltage XLPE cable terminations in Norway. Therefore, measurements of water content have been performed on oil samples taken from several oil-filled housings in service. In addition, measurements of water solubility of three actual oil types have been performed at different relative humidities and temperatures in order to detect the saturation contents. The results show that high water content in the oils in service can be present, and even liquid water was detected. The measurements of water solubility of actual oils show that condensation of water droplets can occur during service. It is therefore recommended to perform maintenance work on such installations with respect to monitor the water content of the insulating oils. Copyright IEEE

Bidragsytere

Knut Brede Liland

  • Tilknyttet:
    Forfatter
    ved Elkraftteknologi ved SINTEF Energi AS
1 - 1 av 1

Resultatet er en del av Resultatet er en del av