Cristin-resultat-ID: 2101859
Sist endret: 9. januar 2023, 10:20
NVI-rapporteringsår: 2022
Resultat
Vitenskapelig artikkel
2022

Parametric study of low-temperature thermal energy storage using carbon dioxide as the phase change material in pillow plate heat exchangers

Bidragsytere:
  • Mahmood Mastani Joybari
  • Håkon Selvnes
  • Erling Vingelsgård
  • Alexis Sevault og
  • Armin Hafner

Tidsskrift

Applied Thermal Engineering
ISSN 1359-4311
e-ISSN 1873-5606
NVI-nivå 1

Om resultatet

Vitenskapelig artikkel
Publiseringsår: 2022
Publisert online: 2022
Trykket: 2023
Volum: 221
Sider: 1 - 16
Artikkelnummer: 119796
Open Access

Importkilder

Scopus-ID: 2-s2.0-85144761872

Beskrivelse Beskrivelse

Tittel

Parametric study of low-temperature thermal energy storage using carbon dioxide as the phase change material in pillow plate heat exchangers

Sammendrag

Industrial low-temperature freezing applications are often batch processes, requiring a lot of energy, exerting stress on the electrical grid. To relieve this stress, thermal energy storage can be used. However, there is a lack of suitable storage material for low temperature applications (around −50 °C). Under high pressures, carbon dioxide can be used as the phase change material for storage temperatures around −55 °C. In this study, a parametric study was conducted on the design and operational parameters of an industrial-scale pillow plate heat exchanger with carbon dioxide. Two responses were selected for the analysis where R1 considered the storage size over the phase change time (kWh/h), while R2 indicated the cost over the storage size (USD/kWh). Using design of experiments, a total of 52 simulations were carried out to investigate the parameters under constant heat transfer surface area. Analysis of variance was then carried out followed by correlation development and optimization. It was found that regardless of the process (charging or discharging), for R1 and R2, the difference between refrigerant and carbon dioxide phase change temperatures followed by plate material had the highest significance. In contrast, the refrigerant flow rate had the lowest significance in almost all cases. Moreover, considering an equal weight for the responses, overall optimal conditions were determined for the processes. The recommended values for plate pitch, plate material, difference between refrigerant and carbon dioxide phase change temperatures and refrigerant flow rate were 25 mm, aluminum, 15 °C and 4 kg/s, respectively.

Bidragsytere

Mahmood Mastani Joybari

  • Tilknyttet:
    Forfatter
    ved Institutt for energi- og prosessteknikk ved Norges teknisk-naturvitenskapelige universitet

Håkon Selvnes

  • Tilknyttet:
    Forfatter
    ved Termisk energi ved SINTEF Energi AS

Erling Vingelsgård

  • Tilknyttet:
    Forfatter
    ved Fiskeri og ny biomarin industri ved SINTEF Ocean
Inaktiv cristin-person

Alexis Gerard Edouard Sevault

Bidragsyterens navn vises på dette resultatet som Alexis Sevault
  • Tilknyttet:
    Forfatter
    ved Termisk energi ved SINTEF Energi AS
Aktiv cristin-person

Armin Hafner

  • Tilknyttet:
    Forfatter
    ved Institutt for energi- og prosessteknikk ved Norges teknisk-naturvitenskapelige universitet
1 - 5 av 5