Cristin-resultat-ID: 1197543
Sist endret: 23. juli 2015, 10:06
NVI-rapporteringsår: 2014
Resultat
Vitenskapelig artikkel
2015

Wideband Modeling, Field Measurement and Simulation of a 420 kV Variable Shunt Reactor

Bidragsytere:
  • Bjørn Alfred Gustavsen
  • Magne Runde og
  • Trond Magne Ohnstad

Tidsskrift

IEEE Transactions on Power Delivery
ISSN 0885-8977
e-ISSN 1937-4208
NVI-nivå 2

Om resultatet

Vitenskapelig artikkel
Publiseringsår: 2015
Publisert online: 2014
Trykket: 2015
Volum: 30
Hefte: 3
Sider: 1594 - 1601

Importkilder

Scopus-ID: 2-s2.0-84930504101

Beskrivelse Beskrivelse

Tittel

Wideband Modeling, Field Measurement and Simulation of a 420 kV Variable Shunt Reactor

Sammendrag

A 420 kV gapped-core five-legged variable shunt reactor is modeled in the frequency range 5 Hz-10 MHz based on frequency sweep measurements and curve fitting. Comparison with time domain measurements at reduced voltage shows that the model can accurately predict the transient behavior of the shunt reactor, both for impinging overvoltages and circuit breaker transient recovery voltages. Among the observations is that mutual coupling between the phases leads to a beat phenomenon in the reactor voltage following disconnection. Representing the shunt reactor by an LC parallel circuit leads to unrealistic results for steep-fronted incoming waves and high-frequency oscillating overvoltages, and for the attenuation of the transient recovery voltage following disconnection.

Bidragsytere

Bjørn Alfred Gustavsen

  • Tilknyttet:
    Forfatter
    ved Energisystemer ved SINTEF Energi AS

Magne Eystein Runde

Bidragsyterens navn vises på dette resultatet som Magne Runde
  • Tilknyttet:
    Forfatter
    ved Elkraftteknologi ved SINTEF Energi AS

Trond Magne Ohnstad

  • Tilknyttet:
    Forfatter
    ved Diverse norske bedrifter og organisasjoner
1 - 3 av 3