Ductless ventilation - Refurbishing an old listed building into modern energy-efficient offices

Bidragsytere:
  • Peter Schild

Presentasjon

Navn på arrangementet: The 11th International Conference on Indoor Air Quality and Climate
Sted: København
Dato fra: 17. august 2008
Dato til: 22. august 2008

Arrangør:

Arrangørnavn: DTU - Danmarks Tekniske Universitet

Om resultatet

Vitenskapelig foredrag
Publiseringsår: 2008

Importkilder

SINTEF AS-ID: S9310

Beskrivelse Beskrivelse

Tittel

Ductless ventilation - Refurbishing an old listed building into modern energy-efficient offices

Sammendrag

This paper presents an application ductless balanced ventilation with heat recovery, non-invasively retrofitted into a naturally-ventilated old building at Akershus Fortress, Oslo. The system exploits the building's architechture to best effect, using original brickwork air stacks, high ceilings and thermal mass. Staircases and corridors transport supply air to each room, and air is exhausted via the stacks. A quality-based cleaning regime minimizes the supply air pollutant load. The paper describes the design studies (CFD, mulitzone airflow and dynamic building thermal modelling), and experiences from 5 years of operation. The air distribution is stable, and contaminant spread is not a problem. Window airing is discouraged to limit infiltration. Simulations indicated that summer overheating is less of a problem than for a ductwork system. Occupants are satisfied with the indoor environment. Hovwever, there remains a teething problem with temperature differences between rooms, due to temperature rise along the supply air flow path.

Bidragsytere

Aktiv cristin-person

Peter Geoffrey Schild

Bidragsyterens navn vises på dette resultatet som Peter Schild
  • Tilknyttet:
    Forfatter
    ved Bygninger og installasjoner ved SINTEF AS
1 - 1 av 1