Cristin-resultat-ID: 1290348
Sist endret: 7. oktober 2019, 19:35
NVI-rapporteringsår: 2015
Resultat
Vitenskapelig Kapittel/Artikkel/Konferanseartikkel
2015

Experimental study on system performance of ultra-low temperature cascade refrigeration system using Carbon Dioxide with tapered evaporator/sublimator

Bidragsytere:
  • Yuhiro Iwamoto
  • Haruhiko Yamasaki
  • Xiao-Dong Niu
  • Petter Nekså og
  • Hiroshi Yamaguchi

Bok

Proceedings of the 24th International Congress of Refrigeration
ISBN:
  • 978-2-36215-012-8

Utgiver

International Institute of Refrigeration
NVI-nivå 1

Serie

Actes du ... Congres international du froid
ISSN 1025-9031
NVI-nivå 1

Om resultatet

Vitenskapelig Kapittel/Artikkel/Konferanseartikkel
Publiseringsår: 2015
Hefte: 2015
ISBN:
  • 978-2-36215-012-8

Klassifisering

Fagfelt (NPI)

Fagfelt: Fysikk
- Fagområde: Realfag og teknologi

Beskrivelse Beskrivelse

Tittel

Experimental study on system performance of ultra-low temperature cascade refrigeration system using Carbon Dioxide with tapered evaporator/sublimator

Sammendrag

CO2 has received extensive attentions in developing various energy conversion systems. In recent years, a CO2 ultra-low temperature cascade refrigeration system with dry ice sublimation has been introduced. The system is composed of two CO2 refrigeration compression cycles, namely high pressure cycle and low pressure cycle, to achieve a cryogenic refrigeration bellow the CO2 triple-point temperature of -56.6℃. In the expansion process of the liquid CO2 at the low pressure cycle, dry ice (solid-gas two-phase flow) is formed, and it has been know that the geometric configuration of the evaporator/sublimator is one of important factors in the CO2 ultra-low temperature cascade refrigeration system. In this report, a tapered evaporator/sublimator is newly designed and installed into the existed CO2 ultra-low temperature cascade refrigeration system in order to investigate the heat transfer characteristics and its associated system performances. Based on the investigation, it is found that the CO2 ultra-low temperature cascade refrigeration system with the tapered evaporator/sublimator has the capability of achieving the ultra-low temperature of -66.3℃ continuously. Resultantly the achieved refrigeration temperature with the tapered evaporator/sublimator is 3.5℃ lower than that of the sudden expansion evaporator/sublimator which is installed in the previous system.

Bidragsytere

Yuhiro Iwamoto

  • Tilknyttet:
    Forfatter
    ved Doshisha University

Haruhiko Yamasaki

  • Tilknyttet:
    Forfatter
    ved Doshisha University

Xiao-Dong Niu

  • Tilknyttet:
    Forfatter
    ved Shantou University

Petter Nekså

  • Tilknyttet:
    Forfatter
    ved Gassteknologi ved SINTEF Energi AS

Hiroshi Yamaguchi

  • Tilknyttet:
    Forfatter
    ved Doshisha University
1 - 5 av 5

Resultatet er en del av Resultatet er en del av

Proceedings of the 24th International Congress of Refrigeration.

IIR., ICR2015. 2015, International Institute of Refrigeration. Vitenskapelig antologi/Konferanseserie
1 - 1 av 1