Contact and nozzle wear from 100 interruptions for a puffer-type air load break switch

Bidragsytere:
  • Nina Sasaki Støa-Aanensen
  • Erik Jonsson og
  • Magne Runde

Tidsskrift

Plasma Physics and Technology
ISSN 2336-2626
e-ISSN 2336-2634
NVI-nivå 1

Om resultatet

Vitenskapelig artikkel
Publiseringsår: 2017
Publisert online: 2017
Volum: 4
Hefte: 1
Open Access

Importkilder

Scopus-ID: 2-s2.0-85048599508

Beskrivelse Beskrivelse

Tittel

Contact and nozzle wear from 100 interruptions for a puffer-type air load break switch

Sammendrag

One type test requirement for medium voltage load break switches is to interrupt 100 consecutive "mainly active loads". A puffer-type switch with axial-blown arc has been tested according to the 630 A/24 kV ratings. The nozzle and contact wear were measured regularly to investigate design requirements and the impact from nozzle wear on gas flow. The contact wear is only moderate, while the nozzle wear causes a decrease in pressure build-up, which in turn may influence the interruption performance.