Cristin-resultat-ID: 2061267
Sist endret: 5. mai 2023, 16:54
NVI-rapporteringsår: 2022
Resultat
Vitenskapelig Kapittel/Artikkel/Konferanseartikkel
2022

Experimental investigation on integrated two-stage evaporators for CO2 heat-pump chillers

Bidragsytere:
  • Armin Hafner
  • Mihir Mouchum Hazarika
  • Federico Lechi
  • Alvaro Zorzin
  • Ángel Á. Pardiñas og
  • Krzysztof Banasiak

Bok

15th IIR-Gustav Lorentzen Conference on Natural Refrigerants - GL2022 - Proceedings - Trondheim, Norway, June 13-15th 2022
ISBN:
  • 978-2-36215-045-6

Utgiver

International Institute of Refrigeration
NVI-nivå 1

Serie

Science et technique du froid
ISSN 0151-1637
e-ISSN 1766-0408
NVI-nivå 1

Om resultatet

Vitenskapelig Kapittel/Artikkel/Konferanseartikkel
Publiseringsår: 2022
Hefte: 2022-15
ISBN:
  • 978-2-36215-045-6
Open Access

Klassifisering

Fagfelt (NPI)

Fagfelt: Energi
- Fagområde: Realfag og teknologi

Beskrivelse Beskrivelse

Tittel

Experimental investigation on integrated two-stage evaporators for CO2 heat-pump chillers

Sammendrag

In this experimental study the performance of novel compact evaporator configuration was investigated. What makes this evaporator configuration unique is the integration of a gravity-fed/ self-circulation evaporator loop on one side of a plate heat exchanger (pre-cooling the secondary flow) and an ejector-assisted circulation loop on the other side (after-cooling the secondary flow). The secondary loop is internally connected, which means that larger temperature differences can be obtained with less connection work and space required, compared to previous heat exchanger models. Current CO2 heat-pump chillers available on the market utilize two evaporators to achieve high energy efficiency values. Space saving of the new compact design is a desired solution from vendors. When using this new concept, only one ‘three-circuit’ brazed heat exchanger is needed. The experimental campaign proofed that an ejector integration enables the two-stage evaporation configuration which significantly elevates the compressor suction pressure and improves the overall system performance. These systems can be applied in several market sectors including industrial chillers with high-capacity demands, where the secondary fluid is cooled even below 0°C.

Bidragsytere

Aktiv cristin-person

Armin Hafner

  • Tilknyttet:
    Forfatter
    ved Institutt for energi- og prosessteknikk ved Norges teknisk-naturvitenskapelige universitet

Mihir Mouchum Hazarika

  • Tilknyttet:
    Forfatter
    ved Institutt for energi- og prosessteknikk ved Norges teknisk-naturvitenskapelige universitet

Federico Lechi

  • Tilknyttet:
    Forfatter
    ved Italia

Alvaro Zorzin

  • Tilknyttet:
    Forfatter
    ved Italia

Angel Alvarez Pardinas

Bidragsyterens navn vises på dette resultatet som Ángel Á. Pardiñas
  • Tilknyttet:
    Forfatter
    ved Termisk energi ved SINTEF Energi AS
1 - 5 av 6 | Neste | Siste »

Resultatet er en del av Resultatet er en del av

15th IIR-Gustav Lorentzen Conference on Natural Refrigerants - GL2022 - Proceedings - Trondheim, Norway, June 13-15th 2022.

IIR, .. 2022, International Institute of Refrigeration. Vitenskapelig antologi/Konferanseserie